BG41 BV Graph

BG41 Battery Voltage analog output switch selectable options

The blue line represents the Battery Voltage analog output with the slide switch pushed to the right.

The red line represents the Battery Voltage analog output with the slide switch pushed to the left.

BG41 BG Graph

BG41 Battery to Ground analog output

When the output is at zero the Battery power system is completely isolated from the Earth grounded power system. The chart above shows a wide range of leakages from completely isolated to direct shorts to the plus and minus terminals of the battery power system for a battery system whose present Voltage is 125V. A direct short from the positive terminal of the battery to Earth Ground will be at +0.8mA. A direct short from the negative terminal of the battery will be at -0.8mA.