BG21 Battery Voltage analog output switch selectable options |
The blue line represents the Battery Voltage analog output with the slide switch pushed to the right. |
The red line represents the Battery Voltage analog output with the slide switch pushed to the left. |
BG21 Battery to Ground analog output |
|||||
When the output is at zero the Battery power system is completely isolated from the Earth grounded power system. The chart above shows a wide range of leakages from completely isolated to direct shorts to the plus and minus terminals of the battery power system for a battery system whose present Voltage is 24V. A direct short from the positive terminal of the battery to Earth Ground will be at +0.8mA. A direct short from the negative terminal of the battery will be at -0.8mA. |